AAAC-6201

Codeword

Size
(AWG or kcmil)

Stranding ACSR of Equivalent Diameter

Wire Diameter
(in)

Overall Diameter
(in)

Cross-Sectional Area
(sq in)

Weight
(lb / 1000 ft)

Rated Strength
(lbf)

DC Resistance @ 20 deg C
(ohm / 1000 ft)

Ampacity
(A)

Size
(AWG or kcmil)

Stranding
(Al/St)

Akron 30.58 7 6 6/1 0.0661 0.198 0.024 28.5 1110 0.659 107
Alton 48.69 7 4 6/1 0.0834 0.250 0.0382 45.4 1760 0.414 143
Ames 77.47 7 2 6/1 0.1052 0.316 0.0608 72.2 2800 0.260 191
Azusa 123.3 7 1/0 6/1 0.1327 0.398 0.0968 114.9 4270 0.163 256
Anaheim 155.4 7 2/0 6/1 0.149 0.447 0.1221 144.9 5390 0.130 296
Amherst 195.7 7 3/0 6/1 0.1672 0.502 0.1537 182.5 6790 0.103 342
Alliance 246.9 7 4/0 6/1 0.1878 0.563 0.1939 230.2 8560 0.0816 395
Butte 312.8 19 266.8 26/7 0.1283 0.642 0.2456 291.6 10500 0.0644 460
Canton 394.5 19 336.4 26/7 0.1441 0.721 0.3098 367.9 13300 0.0511 533
Cairo 465.4 19 397.5 26/7 0.1565 0.783 0.3655 433.9 15600 0.0433 590
Darien 559.5 19 477 26/7 0.1716 0.858 0.4394 521.7 18800 0.0360 663
Elgin 652.4 19 556.5 26/7 0.1853 0.927 0.5124 608.3 21900 0.0309 729
Flint 740.8 37 636 26/7 0.1415 0.991 0.5818 690.8 24400 0.0272 790
Greeley 927.2 37 795 26/7 0.1583 1.108 0.7282 864.6 30500 0.0217 908

Notes:

  1. Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.
  2. Resistance is calculated using metal conductivity of 52.5% IACS for 6201.
  3. Ampacities are based on 75ºC conductor temperature, 25ºC ambient, 2 ft/s wind, full sun, an emissivity of 0.5 and a coefficient of solar absorption of 0.5, at sea level.

Notes:

  1. Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.